Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided Yes No The elevator pit has a re-occurring issue of flooding in the pit. There is no sump pump presently installed in the pit but was a violation issued on the last annual inspection. Sump pump shall be installed in pit. Reinspection required.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.1.1 No No The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Repair pit light fixture. 9/26/2020
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes Yes Hoist ropes are rouged & undersized. Unit is Red-tagged, Re-inspection required 7/25/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Need to provide lighting in machine room to be at least 10 fc at floor 10/9/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Pit has 6" of standing water, needs to be removed. This is a re-occurring issue. Sump pump needs to be installed in pit 10/9/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 No No HVAC unit in machine room is not maintaining manufacturer temperature and humidity recommendations, needs repaired 10/9/2025