Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) No No Telephone in car doesn't work. Heavy interference on phone line when 110ac is turned off to car 5/23/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Phone in car fails to establish two-way communication 5/30/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Phone in car fails to establish two-way communication 10/6/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Phone in car fails to establish two-way communication 6/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Phone loses power when the normal power is removed 6/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Phone loses power when the normal power is removed 5/22/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The emergency light does not illuminate when normal power is removed. 5/22/2026
A17.1-2016 : Elevators 3.20 - Governor rope 8.6.3.4 Yes No The Governor rope was submerged in water when the pit flooded. Replace Governor rope due to excessive corrosion on the section that was submerged. 5/22/2026
A17.1-2016 : Elevators 3.20 - Governor rope 8.6.3.4 Yes Yes The governor rope was submerged under water when the pit flooded. The rope is rusted on the sections that were submerged. Uncorrected violation from 2025. 5/28/2026