Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)9 Capacity Plate Post elevator capacity tag inside elevator
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening. The door restrictor has been made inoperable
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Reduced diameter 5/26/2021
A17.1-2016 : Elevators 1.8 - Door closing force 8.6.4.19.8 x Reduce door closing force to not exceed 30 ft lbs. 5/16/2025
A17.1-2016 : Elevators 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) 8.6.4.19.6 x 8.6.4.19.6 When the car is placed on phase 1 fire service the elevator should recall and hold at the recall floor. The car remains in normal operation after recalling. 5/16/2025
A17.1-2016 : Elevators 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) 8.6.4.19.6 x When the car is placed on phase 1 fire service the elevator should recall and hold at the recall floor. The car remains in normal operation after recalling.
conversion conversion n/a Replace suspension ropes. Reduced diameter 4/5/2018