Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts The car top light does not illuminate
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace broken cab steadier roller on the car top.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening. The door restrictor has been made inoperable
MO Minimum : Elevators (S) - Fire Service (S)1 x Car continues running from second floor and 4th floor on Phase 1 fire service recall 12/23/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x x during Phase 1 Fire service elevator recalls but doesn't hold at the recall floor 6/14/2022
A17.1-2016 : Elevators 1.8 - Door closing force 8.6.4.19.8 x Reduce door closing force to not exceed 30 ft lbs. 5/16/2025
conversion conversion conversion - reinspect x Phase I fire service - Car returns to recall floor then runs to random floors. 4/5/2018