Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Emergency light in car doesn't work 12/2/2019
conversion conversion n/a Door restrictor doesn't work 12/2/2019
MO Minimum : Elevators (I) - Pits (I)3 All elevators shall have counterweight guards. Guards shall be of unperforated metal of at least the strength of or braced to the equivalent strength of number fourteen (14) gauge sheet steel. Guards shall extend from a point not more than twelve inches (12") above the pit floor to a point not less than seven feet (7') above the pit floor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x Phase II Fire Fighters Key Switch operation is intermittently working. The Hold and Off position don't function correctly.
MO Minimum : Elevators (I) - Pits (I)3 All elevators shall have counterweight guards. Guards shall be of unperforated metal of at least the strength of or braced to the equivalent strength of number fourteen (14) gauge sheet steel. Guards shall extend from a point not more than twelve inches (12") above the pit floor to a point not less than seven feet (7') above the pit floor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency light does not work when normal power is removed. The alarm bell still works.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication