Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening. The rubber hood is missing from the hatch latch. 5/8/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening. The rubber hood is missing from the hatch latch. (Reinspect. Outstanding violation from 2025)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Phone in car fails to establish two-way communication 6/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No The door reversal sensor does not cause the door to reverse direction when the beam is broken. (Reinspect)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. 5/8/2026