A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Provide Cat 1 testing.
|
10/29/2024
|
A17.1-2016 : Elevators
|
4.12 - Standby power selection switch
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Provide Cat 1 testing.
|
10/29/2024
|
conversion
|
conversion
|
n/a
|
|
|
Pit lights not working
|
8/1/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
Repair emergency phone.
|
8/13/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
Repair emergency light.
|
8/13/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Elevator phone does not work.
|
6/23/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.11.1 Firefighters' Emergency Operation & Documentation
|
|
|
Monthly firefighters service shall be maintained on site
|
10/22/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Ground landing is missing 2 door gibs on each door. REINSPECT REQUIRED
|
10/22/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Landing 1 is missing a door gib. REINSPECT REQUIRED
|
10/22/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
8/23/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
This elevator has an emergency backup generator that needs to be scheduled & tested. Re-inspection required
|
8/23/2024
|