Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.7 - Car door or gate 2.14.5 Gap between car door and car entrance jamb must not exceed 1/2". 2.14.5.6.4(a) (currently gap in lower right corner exceeds 1")
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Must make Emergency Phone Operable 2/28/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must post current Cert. 3/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.11.2.1.1(e) Car Lighting Must make emergency light operable. 2/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make emergency two way communication operable. 1.6 3/20/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make emergency alarm operable. 2/25/2019