Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)2 Car buffer pit channel rusted out. Need to replace pit channel that car buffer is mounted on. 4/21/2021
MO Minimum : Elevators (I) - Pits (I)2 Counterweight buffer and pit channel rusted. Need replacement and permanent mounting of same. 4/21/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x During phase 2 operation the rear doors reopen after they are fully closed and the door close button is released 10/24/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency bell does not operate 8/8/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone dialing wrong number. Reprogram and retest.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone on car operating panel does not operate. 10/24/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Front doors do not close under power during fire recall 10/24/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x No fire alarm initiating devices located in the elevator lobbies or in the machine room 10/24/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No fire extinguisher in machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No maintenance records
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No MCP
MO Minimum : Elevators (I) - Pits (I)5 Pit ladder rusted at bottom of ladder. Repair or replace ladder and resecure to wall.
MO Minimum : Elevators (I) - Pits (I)1 Pits need to be kept dry 4/21/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate inside machine room. 4/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Post emergency evacuation of passengers form inside machine room. 4/21/2021
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post firefighter operating instructions next to fire keyswitch on car operating panel
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post firefighter operating instructions next to hall fire keyswitch
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post firefighter operating instructions next to hall fire keyswitch
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post firefighter operating instructions next to hall fire keyswitch and on car operating panel. 4/21/2021
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post firefighter operating instructions on car operating panel
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post firefighter operating instructions on car operating panel and next to hall fire keyswitch
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage next to hall button fixture at each landing
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage next to hall button fixture at each landing
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Provide smoke detectors at each lobby, and machine room and test.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide type ABC fire extinguisher inside the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly 4/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation Test and log firefighter operation monthly