Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No Need to post fire service instructions inside and outside elevator 4/21/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Test and log firefighter operation monthly 4/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Post In Case of Fire signage next to the hall button fixture at each landing
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal No No No visual or audible signal during fire recall.
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Replace incorrect firefighter phase 2 instructions on the car operating panel.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door not latching, or locking closed, repair.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Post emergency evacuation of passengers form inside machine room 4/21/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate inside machine room 4/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation No No Test and log firefighter operation monthly
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state operating certificate inside the machine room
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room access door needs to be self-locking
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal No No No visual signal during fire recall operation.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Post In Case of Fire signage next to hall button fixture at each landing
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No No MCP
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No No maintenance records on site
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door needs to be self-locking
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not operate 10/22/2024
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No No visual or audible signal inside elevator during fire recall operation 8/11/2022
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No No audible or visual signal in firefighter recall 8/10/2021