Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Post emergency evacuation of passengers form inside machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate inside machine room
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove flammable rags from machine room floor.
MO Minimum : Elevators (I) - Pits (I)1 Remove hydraulic oil from pit floor
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams Remove spare parts for the elevator from the controller. The controller cabinet is not a storage container.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door lock needs to be self-locking and non-defeatable.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door needs to be self-locking
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams Spare parts can not be stored inside elevator controller.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No MCP on site
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No maintenance records on site
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed in machine room
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door needs to be self-locking
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove rags from machine floor
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams Remove spare parts from the controller cabinet. Controller cabinet is not a storage container
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not work
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed
MO Minimum : Elevators (H) - Machine Rooms (H)2 Provide a self locking door knob for machine room door.