MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Test and log firefighter operation monthly
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Post emergency evacuation of passengers form inside machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate inside machine room
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove rags and other flammable items from machine room floor.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger pump from pit. Cylinder drain line should drain into pit container of no more than 5 gallon capacity
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Replace missing roller on up direction speed limiting switch.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.11.1 Firefighters' Emergency Operation & Documentation
|
|
|
Test and log firefighter operation monthly
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Identify the inside of hoistway doors with a numeral corresponding to the landing floor
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace roller on up speed limiting switch with roller of equivalent strength, material, and design
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.7.2 Periodic Test Record (Test Tags)
|
|
|
Install metal test tag for periodic pressure relief test
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
No maintenance control plan on site
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
No maintenance records on site
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light does not illuminate
|
2/2/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove non-elevator related material from machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light and bell do not operate
|
10/21/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace missing car direction lantern lenses
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove all non elevator related items from machine room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room expired.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Bottom directional switch not working, contact with buffers during test.
|
|