Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide a maintenance control program on site 8/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x In car communication system not working 6/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods jumper left on controller unit will not run without it. Needs to be corrected and reinspect in 30 days or red tag will be put on equipment 6/8/2022
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x Fire Service recall buzzer not working on phase 1 recall 10/8/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices x x Phase 1 fire service did not recall elevator red tagged out of service 8/18/2023