Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage There is no fireman's emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Emergency light/bell battery 7/26/2019
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure x emergency telephone handset not working. 6/16/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 7/13/2020