A17.1-2016 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.10.2.3 Toe Board
|
x
|
|
When performing the unintentional movement test, the elevator car top struck the top of the hoist way damaging the railing on top of the car. The railing shall be repaired, no reinspection required.
|
8/28/2020
|
A17.1-2016 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.10.2.3 Toe Board
|
x
|
|
When performing the unintentional movement test, the elevator car top struck the top of the hoist way damaging the railing on top of the car. The railing shall be repaired, no reinspection required.
|
9/27/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair alarm bell.
|
9/18/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.2.1.1(e) Car Lighting
|
|
|
Repair car light cover.
|
12/1/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.2.1.1(e) Car Lighting
|
|
|
Repair emergency light.
|
12/1/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6
|
x
|
|
Provide Phase II operations to be proper, car would not return to Phase I recall when Phase II is turned off.
|
9/27/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.42 Seismic (Earthquake protection)
|
8.4.10
|
|
|
Repair ring and string. 8.4.10.1.2 (c)
|
12/1/2018
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
8.6.4.20.11 (Re-Inspection)
|
x
|
x
|
Upon performing the required unintentional movement test, the rope gripping device failed to actuate within 48” as required. The elevator has been placed out of service at this time and a red tag issued. The rope gripping device shall be repaired and a reinspection shall be performed before the elevator can be returned to service.
|
8/28/2020
|