Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits water/oil in pit 7/8/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits oil in pit--elevator needs to have new packings install 7/8/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits oil in pit--clean--repack 7/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone not working 2/14/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.35 - Supply Line and Shutoff Valve 3.19 Overspeed valve has seal but not dated. Needs to be tested unless a proper date can be confirmed 2/14/2025
conversion conversion n/a oil/water in pit 7/8/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine door does self close but can be left in unlocked position. Needs to only able to open from outside by a key 2/14/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Sump pump piping runs directly over elevator machine & controller piping is not guarded or guttered.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone failed to operate appears phone line has been removed.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Light does not give off enough illumination to provide the required lighting at floor lever in front of controller.
MO Minimum : Elevators (H) - Machine Rooms (H)8 Lighting in machine room is hanging from the ceiling, secured only by wire nuts.
MO Minimum : Elevators (I) - Pits (I)1 Oil in pit- clean 12/13/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is out of date 2/14/2025