ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
|
|
Repair the landing sill of the broken concrete, 2 inch wide crack at the entrance lower leve. This will elemonate the trip hazard.
|
10/15/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair the emergency phone as the line is dead, call for re-inspection within 14 days.
|
1/24/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Remove the added file cabinet and shelves from the elevator machine room. This is not a store room.
|
5/10/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.11.2.1.3(w)
|
|
|
Repair or replace the fast speed door 2nd. landing as the door has been damaged by someone hitting it with the pallet jack and broke the welds along the bottom brace and side rail allowing it to drag and wear the sill excessivily.
|
10/15/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump pump shall be provided
|
x
|
|
Repair the electrical to the sump pump as it will not pump and the receptical is dead.
|
9/7/2022
|