MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Need to post fire service instructions inside and outside the elevator.
|
6/22/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
No Montly Fire service test log
|
3/2/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Must make doors inoperable on phase I after reaching designated floor.
|
6/1/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Must provide Fire service instructional Signage in car and hall. 8.11.2.1.1(o)
|
6/1/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must post Current State Operating Cert. 5.100(2)
|
8/1/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Test fire service operation monthly and provide documentation.
|
8/2/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Need to provide minimum of 10 foot candles of lighting on machine room floor.
|