Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Emergency phone does not operate 10/23/2018
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Governor rope has excessive amount of wire breaks and needs to be replaced 6/22/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x Need to post fire service instructions inside and outside the elevator. 6/22/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x Visual and audible signals do not operate when elevator is on fire service. 6/22/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x Smoke senstive door reopening device is not disabled during fire service phase2 operation. 6/22/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test fire service operation monthly and provide documentation. 3/2/2023
MO Minimum : Elevators (S) - Fire Service (S)1 x x Visual (light) and audible (buzzer) signal do not function during fire recall operation. Not red tagged 4/28/2021
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x Must make Visual and Audio Fire service signal operable 6/1/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Must provide Fire service operational instructions both car and hall 3/2/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Must provide monthly fire service test log 3/2/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate 5.100(2) Must post Current state operating Cert. 5.100(2) 8/1/2023