ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.16 -Overhead Beam and Fastenings
|
2.9.1
|
|
|
Welds are broken where machine beams are welded to floor supports
|
2/14/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
Machine rooms shall be provided with natural or mechanical means to keep ambient air temperature and humidity in the range specified by the elevator manufacturer to ensure safe & normal operation of the elevator, should be posted in the machine room
|
2/14/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Class ABC fire extinguishers shall be provided in the machine room, located convenient to access door
|
2/14/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Need maintenance control program on site posted on controller
|
2/14/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Welds are broken where machine beans are welded to floor support
|
2/14/2023
|