Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need maintenance control program on site posted on controller 2/10/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 Machine rooms shall be provided with natural or mechanical means to keep ambient air temperature and humidity in the range specified by the elevator equipment manufacturer to ensure safe & normal operation of the elevator, needs to have temperature & humidity range posted in machine room. 2/10/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Class ABC fire extinguishers shall be provided in machine room and convenient to access door. 2/10/2023
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) x Counterweights land on spring buffer when elevator is on final limit. Shorten hoist cables for more runby clearance. Re-inspection required