ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Class ABC fire extinguishers shall be provided in machine room and convenient to access door.
|
2/10/2023
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11 Runby (Re-Inspect)
|
x
|
|
Counterweights land on spring buffer when elevator is on final limit. Shorten hoist cables for more runby clearance. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
Machine rooms shall be provided with natural or mechanical means to keep ambient air temperature and humidity in the range specified by the elevator equipment manufacturer to ensure safe & normal operation of the elevator, needs to have temperature & humidity range posted in machine room.
|
2/10/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Need maintenance control program on site posted on controller
|
2/10/2023
|