MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
maintenance control program (MCP) documents shall be available in the machine room
|
2/23/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
need to perform and log the monthly fire service test, keep log in the machine room
|
2/23/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
replace burnt out pit light bulb
|
2/23/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
|
|
adjust car door closing and opening, it slams open and close
|
2/23/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
did not have Maintenance Control Program (MCP) documents in the machine room
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
monthly fire service test log is not being filled out monthly
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
repair the machine room door, the door has swelled and rusted so that it can only be opened with pry bars
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
water in pit, pit equipment showing signs of rust, prevent the accumulation of ground water in the pit
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)10 Car Floors
|
|
|
Repair/replace broken tiles on the elevator cab floor, tripping hazzard
|
3/19/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Water in pit, pit equipment showing signs of rust, prevent the accumulation of ground water
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
the emergency phone did not work, the phone line was dead at the controller, provide working phone line to the elevator controller
|
3/12/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work, provide working phone line
|
8/6/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
reprogram elevator, fire service did not work at all
|
1/7/2022
|