MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
emergency light battery is weak, the lights dim when the alarm button is pushed, the battery needs to be replaced
|
8/23/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)6
|
|
|
label controller, tank, disconnects, car operating panel, pit and car top Elevator #3
|
1/26/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
the fire service relays in the machine room are hanging by their wires out of the electrical box, relays need to be properly secured to the electrical box
|
1/26/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
x
|
x
|
the fire service phase 1 keyswitch did not work, repair the keyswitch
|
3/12/2020
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection)
|
|
|
the fire hat jewel in the car operating panel did not light during phase 1 recall.
|
1/26/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection)
|
|
|
phase 1 fire service recall audible signal did not work
|
1/26/2022
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Replace burnt out cab ceiling lights, required to have 5 foot candles of illumination inside the elevator and minimum of two bulbs
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
provide a record of findings for firefighters' service operation
|
12/15/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
The Maintenance Control Program (MCP) On-Site documents are not in the machine room.
|
1/26/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
does not have Maintenance Control Program (MCP) documents in the machine room
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
the monthly firefighters service test log is not being filled out monthly
|
1/26/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
the monthly fire service test log in the machine room is not being filled out monthly
|
|