Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)14 Top floor hoistway door sight guard is missing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)2 Alterations Replace "Use Stairway" sign on top floor. 7/8/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire Service Phase I and II not working. Red tagged 6/9/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency alarm does not work on battery power. Re-inspection required 5/19/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Alarm bell does not work on battery back up 5/17/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit appears to have emergency generator power, which needs to be tested and witnessed by an inspector to complete the inspection. Re-inspection required