Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Phone in elevator cab does not work 6/7/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit appears to have emergency generator power, which needs to be tested and witnessed by an inspector to complete the inspection. Re-inspection required 3/3/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevator placed in Inactive status, testing could not be completed at this time. Inactive status is only alllowed for 2 years at which time the elevator shall be returned to service or decommissioned according to the state of MO requirements. A Cat 5 test shall be performed before the elevator can be returned to service. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit appears to have emergency generator power, which needs to be tested and witnessed by an inspector to complete the inspection. Re-inspection required
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Repair machine room lighting. 7/8/2019