Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.3.1.3(x) Under diameter
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 8.11.3.1.2(f) Replace lamps in machine room lighting
MO Minimum : Elevators (A) - Hoistways (A)3 Car door shall cover full with of opening, as per A17.1 2016 2.14.4.7.4 Requires reinspection in 15 days
MO Minimum : Elevators (I) - Pits (I)1 Remove dirt and rubbish from pit floor
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine room requires housekeeping
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Provide mcp in machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Provide current state operating certificate
MO Minimum : Elevators (I) - Pits (I)1 Remove all dirt and rubbish from pit floor
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Ropes are under-sized and needs replaced 2/1/2023
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9 x Hoise rope elds must be seized with metal not plastic tape. 2.20.9.7.2 2/1/2023
A17.1-2016 : Elevators 2.27 - Rope fastenings 8.11.2.1.2(cc) x Must provide Rope date tag on Hoist ropes . 2.20.2.2.1 2/1/2023