Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Phone failed 2/14/2023
MO Minimum : Elevators (H) - Machine Rooms (H)1 Install Gard rail on ladder that allows egress to machine room (height of approximately 25' with an angle of 70% ) 5/15/2024
MO Minimum : Elevators (H) - Machine Rooms (H)1 Ladder for Egress/Access to equipment room needs a back cover ladder approximately 25' @ an angle of about 75 degree.
MO Minimum : Elevators (H) - Machine Rooms (H)4 Clean Machine Room 5/15/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Ropes under sized 5/20/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Need current operating certificate 10/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No Maintenance Records 5/15/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No Records
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation Fireman's recall is to be checked monthly 5/15/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Phase I key switch requires replacing 5/15/2024
conversion conversion n/a Need current operating certificate posted in machine room. 5/15/2024
conversion conversion n/a Gate switch breaks over 2"- Reduce/adjust 5/15/2024
conversion conversion n/a Replace GFCI in pit 5/15/2024
conversion conversion n/a Door torque over 30 pounds. Adjust 5/15/2024
conversion conversion n/a Need current fire extinguisher in machine room 5/15/2024