Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Gate switch breaks over 2"- Reduce/Adjust 3/25/2020
conversion conversion n/a Need current operating certificate posted in machine room 3/25/2020
conversion conversion n/a Replace GFCi in pit 3/25/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Need current operating certificate 3/25/2020
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine Room needs cleaning
MO Minimum : Elevators (H) - Machine Rooms (H)1 Install Gard rail on ladder that allows egress to equipment room. (Ladder approximately 25" at an angle of 70* with no back Gard)
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Hoist ropes roughing/required to be replaced 2/11/2022
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Unit has been RED TAGGED Could not preform 125% brake test would not pick load 2/11/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Hoist ropes showing roughing under sized 2/14/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No records
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation To be checked monthly
MO Minimum : Elevators (H) - Machine Rooms (H)1 Access ladder to equipment room has no back guard railing 25' rise with an angle of approximately 70 degrees
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Phase I key switch needs replacing
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Under sized required to be replaced 5/20/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No records