Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.24.8.3 x 2.24.8.3(c) & 2.19.1 cable governor does not actuate off governor switch 5/2/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.1 - Door Re-opening device 2.13 2.13.5.1 device stops door from closing on phase II 7/2/2019
conversion conversion n/a emergency light needs battery 7/2/2019
MO Minimum : Elevators (A) - Hoistways (A)16 Replace missing interlock cover @2nd floor, exposed wiring 7/30/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 2-way communication device shall give proper location message, not able to give proper location (REINSPECTION REQUIRED) 8/13/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 2-way communication device shall give proper location message, not able to give proper location (REINSPECTION REQUIRED) 8/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 Fire caulk/fill holes and voids in Hoistway walls 3/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly. 3/22/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.22 - Wire rope fastening and hitch plate 8.6.3 x Hoist Rope tails are missing clips. Replace as needed. 3/22/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.8 - Top emergency exit 8.11.2.1.3(l) Top emergency exit shall be secured. 3/22/2023