Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 12/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 9/2/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Adjust or replace pump motor belts for proper operation. 9/2/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Adjust the hydraulic valve for smother acceleration. 9/2/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)4 x All gates and doors shall comply to A17.1 - 1955, Rule 204.4 - The distance from the face of the hoistway door to the face of the car gate shall not exceed 4 inches. (Re-inspection required in 30 days) 2/21/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Correct oil leaks at valve. 9/2/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a current MO State operating certificate in the machine room. 9/2/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing and self-locking. 9/2/2022
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Pit needs to be cleaned. 5/17/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit shall have a permanent light fixture installed. 9/2/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 12/14/2021
MO Minimum : Elevators (I) - Pits (I)5 Where the depth of any pit is 4 feet or more it shall have a ladder permanently installed. The ladder shall extend not less then 30 inches above the sill of the access door, or hand grips shall be provided to the same height. The ladder shall be of noncombustible material. 9/2/2022