Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.5.8 - Possible single bottom jack. Provide documentation that jack is not a single bottom type. 8/30/2018
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. Water is flowing into the pit from the base of the jack. 6/10/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 12/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 9/2/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing and self-locking. 9/2/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a current MO State operating certificate in the machine room. 9/2/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. 5/10/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)4 x All gates and doors shall comply to A17.1 - 1955, Rule 204.4 - The distance from the face of the hoistway door to the face of the car gate shall not exceed 4 inches. (Re-inspection required in 30 days) 2/21/2023