MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Cab lights shall be guarded.
|
6/10/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
8.6.5.8 - Possible single bottom jack. Provide documentation that jack is not a single bottom type.
|
6/10/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
8.6.5.8 - Possible single bottom jack. Provide documentation that jack is not a single bottom type.
|
6/10/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
12/14/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
9/2/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing and self-locking.
|
9/2/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display a current MO State operating certificate in the machine room.
|
9/2/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. The fire extinguisher is expired.
|
5/10/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)4
|
x
|
|
All gates and doors shall comply to A17.1 - 1955, Rule 204.4 - The distance from the face of the hoistway door to the face of the car gate shall not exceed 4 inches. (Re-inspection required in 30 days)
|
2/21/2023
|