Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x B(11)/1.6.1/8.11.2.1.1(f)/8.6.4.15 : 2-way communication device shall work and give proper location (REINSPECTION within 30 days) 2/8/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x B(11)/1.6.1/8.11.2.1.1(f)/8.6.4.15 : 2-way communication device shall work and give proper location (REINSPECTION within 30 days) 2/8/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 2-way communication device (princess phone) is false calling Atlas Security constantly, per Atlas Dispatch. Repair or replace. Phone does work. 4/1/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 H(2) / 101.3d(1)(b) Machine room door shall be self-closing and self-locking 3/10/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 H(2) / 101.3d(1)(b) Machine room door shall be self-closing and self-locking 2/8/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 H(2) / 101.3d(1)(b) Machine room door shall be self-closing and self-locking 2/8/2021
MO Minimum : Elevators (H) - Machine Rooms (H)8 Fire service overlay battery backup failed. Repair/replace and remove extension cord running across floor. 3/10/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records G(1)/A17.1-2016:8.6.1.4 :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly. 3/10/2022