MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lights do not work.
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
A fire sprinkler discharge head has been added to the elevator machine room. A shunt trip disconnect shall now be added which shall be electrically tied into a heat detector to remove power from the elevator before the application of water per the requirements of NFPA 13, NFPA 72, and NFPA 70. Reinspection and testing will be required. Note RD that A17.1 2016 was not an option in the drop down box.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light is not working
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4 (Re-Inspection)
|
x
|
|
A fire sprinkler discharge head has been added to the elevator machine room. A shunt trip disconnect shall now be added which shall be electrically tied into a heat detector to remove power from the elevator before the application of water per the requirements of NFPA 13. Re-inspection required
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency lights do not work.
|
8/4/2020
|