MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
non elevator items in machine room space need to be removed
|
1/22/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
In car stop sw. working when car in flight
|
9/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
elel not closing doors automatically whan at a floor above main an not returning to main
|
9/3/2020
|