MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work on emergency power or normal power. Re-inspection required
|
11/22/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work on emergency power or normal power. Repair or replace
|
10/27/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lighting shall be have a minimum of 10 foot candle at the controller
|
9/18/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Elevator pit shall be clean on all dirt and debris and cigarettes
|
9/18/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean and dry. Repair sump pump.
|
12/4/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
There is water standing in the pit.
|
12/4/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean and dry
|
12/5/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Pit sump hole shall be covered with a non combustible lid
|
12/5/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Pit sump hole shall be covered with non-combustible lid, flush with the floor.
|
12/4/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current operating certificate shall be on display in the machine room
|
9/25/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher is overdo for annual maintenance, need to perform maintenance
|
9/25/2023
|