Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Hydraulic pump in machine room is leaking fluid from seals. Repair/replace pump. Re-inspect in 30 days 11/17/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Need to test elevator for operation on emergency power. Re-inspection required
MO Minimum : Elevators (A) - Hoistways (A)3 Replace broken pick up rollers on 1st, 2nd, and 3rd level. 7/7/2021