Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 yuo can just walk up an pull the machroom door open it does have the proper door lock but it doesnt latch
MO Minimum : Elevators (H) - Machine Rooms (H)8 wiring from machroom disconnect to controller to small for application whats ther is 4 wire j cord size 8 need 4AWG for application
MO Minimum : Elevators (I) - Pits (I)1 debris in pit 12/4/2019
MO Minimum : Elevators (I) - Pits (I)1 dirty pit needs cleaned
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Provide maint control program on site documentation. 12/3/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt. displayed
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt. posted