Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No 3.26.10 - The auxiliary power lowering operation shall be functional. 8/5/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No In electrical equipment rooms, the illumination shall not be controlled by automatic means. This switch is currently a motion sensor. 8/1/2022