Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)8 2.26.4.1 - Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. 8/1/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x 3.26.10 - The auxiliary power lowering operation shall be functional. 8/5/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 In electrical equipment rooms, the illumination shall not be controlled by automatic means. This switch is currently a motion sensor. 8/1/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The auxiliary power lowering operation shall be functional. 6/28/2024