MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency Phone did not work, phone line dead
|
6/13/2019
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)2
|
x
|
|
could not run car to the top finial, counterweight buffered out before activating the top finial switch. moved the top limit switch as far down as we could (right on top of the top directional switch) still could not acivate the switch before the counterweight buffered out.
|
6/13/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
did not have test weights to perform the 5 year portion of the test
|
5/27/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
emerrgency phone does not have a working phone line, provide working phone line to the elevator controller
|
12/30/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
machine room fire extinguisher is to be inspected and tagged annually, there wasn't a tag on the machine room fire extinguisher indicating when it was last inspected
|
5/27/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
a copy of the state operating certificate is to be posted in the machine room
|
5/27/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
provide maintenance control program on site documentation
|
5/27/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The emergency lights and bell did not work, repair the emergency light system, suspect that the battery is dead
|
6/18/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Replace burnt out machine room light bulbs
|
10/4/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The emergency lights did not work
|
10/4/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
top of car inspection station did not work in the down direction, could not complete the inspection
|
10/5/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
one of the car light fixtures had been removed leaving bare 110 volt live wires exposed hanging out of the ceiling, cap wires and or install replacement fixture
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Live wires with nut caps hanging out of the ceiling, second light fixture is missing
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Oil on cartop leaking into cab, oil dripping off the beams at the top of the hoistway. Clean up oil and address the source
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)1
|
|
|
Need to guard the cab fan from the inside of the cab so that accidental contact with the fan blades cannot happen. there isn't a drop ceiling or grill cover on the cab fan
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Machine room, fire extinguisher inspection tag expired in 2022
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Replace burnt out machine room lightbulbs
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone did not work
|
8/2/2024
|