Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x New phone system requires battery back up 10/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working, alarm bell ok. 2/9/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x PHONE NOT WORKING (NO SIGNAL OF ANY KIND) 2/9/2024
MO Minimum : Elevators (H) - Machine Rooms (H)8 New telephone wiring required to be in conduit 10/27/2022
MO Minimum : Elevators (I) - Pits (I)1 standing oil in pit from leaking packing
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) PIT LIGHT NOT WORKING 2/9/2024
MO Minimum : Elevators (I) - Pits (I)1 REMOVE DEBRIS FROM PIT 2/9/2024
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) PROVIDE REQUIRED PIT LIGHTING 10/24/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) x PHONE NOT RINGING SECURITY 10/24/2024