Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No 1) Where an alteration is made to firefighters’ service operation (see 8.7.2.28), tests shall be conducted as specified in 8.10.2.2.6. Ref: 8.10.2.3.2(m) 5/25/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Firefighter's Emergency Phase II and smoke/sensors still need to be tested to remove red tag. 6/23/2021
MO Minimum : Elevators (D) - Brakes (D)2 Yes Yes 3) The brake shall be capable of holding the car at rest with its 125% rated load, for 5-year testing. 10/4/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No 2) Car-door or gate mechanical and electrical components shall be maintained to ensure safe and proper operation including door restrictors. 10/4/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No 1) Emergency operation of signaling devices, lighting, communication and ventilation, shall be maintained. Phone not working on power outage. 10/4/2019
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes The elevator car safeties failed to apply when the governor was mechanically set. The elevator was tagged out of service and the power disconnected. The elevator shall be repaired and a re-inspection shall be performed before the elevator is returned to service. 6/4/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency generator power indicator light did not work, needs repaired. Re-inspection required 11/25/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency generator power indicator light did not work, needs repaired. Re-inspection required