A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency generator power indicator light did not work, needs repaired. Re-inspection required
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
1) The two-way communication means shall provide on demand to authorized personnel, information that identifies the building location and elevator number. No message heard to authorized personnel. This elevator had a major alteration in 2019. Ref: 2.27.1.1.3(d)
|
8/27/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Firefighter's emergency Phase II needs to be tested. Smoke and heat sensors shall be tested to remove red tag.
|
6/23/2021
|