Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 1) Emergency operation of signaling devices, lighting, communication and ventilation shall be maintained. Bell not functioning correctly on battery power. Ref: 8.6.4.15 8/27/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 3) For systems where the part of cylinder and/or piping is not exposed for visible examination, a written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. Pump for oil returning to tank needs to be removed and replaced by a 5 gallon container. Ref: 8.6.5.7 10/27/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not permit two-way communication. 6/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x 1) All landing-door mechanical and electrical components shall be maintained to ensure safe and proper operation including hoistway door unlocking devices. Per 8.6.4.13.1(e), 1st floor (2nd landing) pickup rollers are not stationary. 9/10/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x x 2) The key switches required by 2.27.2 through 2.27.5 for all elevators in a building shall be operable by the same key. All keys in this building shall be FEO-K1 key. Ref: 2.27.8 8/27/2020