Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No Phase I & II signs 7/11/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate No data plate 7/11/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Must make Fire service phase I and Phase II instructional signage readable. 8.6.1.6.7 7/11/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Ck Monthly 7/11/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) Must Replace and Maintain missing or None readable Phase I and II instructional signage 2.27.7 7/11/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must Post Current State operating Cert. in Machine Room. 5.100(2) 7/11/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must post Current Cert. in machine room 5.100(2) 7/11/2023