Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting 1.5.1(b) Auxiliary Illumination. Emergency Lighting not working in car. 12/3/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency lights and alarm bell do not work. 12/3/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Anti-rotation means on counterweight side of hoist ropes was broken, replace. 11/16/2020
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be clean & dry, pit has water in it 3/29/2024
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Upon performing the required 5-yr full load test, the elevator safety governor was found to be worn to a degree that the activation would not set consistently. Repair or replacement required before returning to service. 2/4/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The machine room was only inspected before the drive motor failed to operate. Reinspection is required. 2/6/2024
conversion conversion n/a Emergency light shall work 11/15/2017
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room 3/29/2024