Emergency light shall work
|
11/15/2017
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
1.5.1(b) Auxiliary Illumination. Emergency Lighting not working in car.
|
12/3/2018
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Upon performing the required 5-yr full load test, the elevator safety governor was found to be worn to a degree that the activation would not set consistently. Repair or replacement required before returning to service.
|
2/4/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency lights and alarm bell do not work.
|
12/3/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Anti-rotation means on counterweight side of hoist ropes was broken, replace.
|
11/16/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be clean & dry, pit has water in it
|
3/29/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. The machine room was only inspected before the drive motor failed to operate. Reinspection is required.
|
2/6/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current operating certificate shall be displayed in the machine room
|
3/29/2024
|