ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
Door restrictor is mechanical type. Found to be out of adjustment on several floors. Repair as needed.
|
12/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection)
|
x
|
|
Hoist ropes showing rouge. Measured, found to be undersized. Replace
|
12/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
|
3/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
The pit light fixtures failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five foot candles at the pit floor for maintenance & emergency personnel.
|
3/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection)
|
x
|
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:- The audible signal device did not sound when phase I was activated. Reinspection is required.
|
2/6/2024
|
conversion
|
conversion
|
n/a
|
|
|
FULL LOAD INSPECTION - ISSUE CERTIFICATE, CHANGE 5 YR. DATE
|
9/18/2017
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current operating certificate shall be displayed in the machine room
|
3/29/2024
|